POWER SUPPLY |
: 4-20 mA : 12 to 30 VDC 0-10 V : 18 to 30 VDC |
---|---|
ACCURACY |
: ± 1 °C Tdc |
REPEATIBILITY |
: ±0.2% of F.S |
HYSTERESIS |
: ±0.2% of F.S |
NON-LINEARITY |
: ±0.3% of F.S |
STABILITY |
: ±0.5% of F.S / Year |
RANGE |
: Programmable from -40° and 100° Tdc. |
RESPONSE TIME |
: 4 s in fairly still air. |
DEFAULT RANGE |
: -20 to 60 ° Tdc |
TEMPERATURE |
— |
T - ACCURACY |
: ±0.5% of F.S |
T - REPEATIBILITY |
: ±0.1% of F.S |
T - RANGE |
: Programmable between -40° and 100°C. |
T - RESPONSE TIME |
: up to 30s in fairly still air. |
T - DEFAULT RANGE |
: 0 to 50°C |
GENERAL FEATURES |
— |
OUTPUT |
: ADP14-DM-C 4-20 mA ADP14-DM-V 0-10 Vdc |
ISOLATION BETWEEN OUTPUTS |
: Isolated 4-20 mA outputs. Non-isolated 0-10 Vdc outputs. |
OUTPUT LOAD (RL) |
: Model 4-20 mA: 600 Ω Model 0-10Vdc: 10 KΩ Minimum |
: |
Internal protection against reversed voltage wire polarity. |
CABLE INPUT |
: PG7 cable gland. |
OPERATIONAL LIMITS |
: Sensor and Probe (ADP14-DM): refer to the diagram below. Electronic Module: -10° to +65°C, 0 to 95%RH. |
PROTECTION |
: IP65, Fireproof ABS, UL94V0 |
CALIBRATION PROTOCOL |
: COML |
The ADP14-DM transmitter series incorporate the best high accuracy and great stability relative humidity and temperature sensors. They convert the measured values into linear 4 to 20 mA signals or 0 to 10 Vdc output can also be offered under request
The microprocessor based circuit enables full configuration of output range when used with the TxConfig PC interface and the Windows based software.
The sensor can be configured for dewpoint and absolute humidity.
Validate your login